Signal targets for E_DIGITAL
Signal
Meaning
E_DIGITAL.0
Digital input 8 (DI/DO 8)
E_DIGITAL.1
Digital input 9 (DI/DO 9)
E_DIGITAL.2
Digital input 10 (DI/DO 10)
E_DIGITAL.3
Digital input 11 (DI/DO 11)
E_DIGITAL.4
Digital input 12 (DI/DO 12)
E_DIGITAL.5
Digital input 13 (DI/DO 13)
E_DIGITAL.6
Digital input 14 (DI/DO 14)
E_DIGITAL.7
Digital input 15 (DI/DO 15)
E_DIGITAL.8
Digital input 0 (DI 0)
E_DIGITAL.9
Digital input 1 (DI 1)
E_DIGITAL.10
Digital input 2 (DI 2)
E_DIGITAL.11
Digital input 3 (DI 3)
E_DIGITAL.12
Digital input 4 (DI 4)
E_DIGITAL.13
Digital input 5 (DI 5)
E_DIGITAL.14
Digital input 6 (DI 6)
E_DIGITAL.15
Digital input 7 (DI 7)
<1> Used in telegrams 390, 391 and 392.
1
2
DO: CU_S
PROFIdrive - E_DIGITAL interconnection
Interconnection
parameters
p2082[0] = r0722[8]
<2>
p2082[1] = r0722[9]
<2>
<2>
p2082[2] = r0722[10]
<2>
p2082[3] = r0722[11]
<2>
p2082[4] = r0722[12]
p2082[5] = r0722[13]
<2>
p2082[6] = r0722[14]
<2>
<2>
p2082[7] = r0722[15]
p2082[8] = r0722[0]
p2082[9] = r0722[1]
p2082[10] = r0722[2]
p2082[11] = r0722[3]
p2082[12] = r0722[4]
p2082[13] = r0722[5]
p2082[14] = r0722[6]
p2082[15] = r0722[7]
<2> Can be set via p0728 as input (DI) or output (DO).
3
4
[Function diagram]
[Function diagram]
<3>
Internal status word
signal target
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
<3> Pre-assignment, can be freely changed.
5
6
Function diagram
fp_2459_01_eng.vsd
SINAMICS S
22.02.07 V02.05.00
PROFIdrive sampling time
<1>
Refer to [1020.7]
Inverted
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7
8
- 2459 -