Rated motor temperature rise
Calculated motor temperatures
Mot T_environment
p0625[M]
Mot T_on iron
p0626[M]
Thermal
3-mass-model
Mot T_on stator
(for induction motors
p0627[M]
only)
Mot T_on rotor
p0628[M]
Model tracking
Mot temp_sensor
p0600[M]
Nur
bei
0
KTY
from encoder 1
1
[4704.8]
from encoder 2
2
[4704.8]
from encoder 3
3
[4704.8]
from Motor Modules
or CUA31
11
Mot temperature [°C]
p0603[C]
10
[9576.3]
(0)
e.g. r4105 from TM31
<1> For KTY and PTC, the value p0606 = 0 has a different meaning:
KTY: 0
The output of the timer is always switched out (logical 0)
PTC: 0
Delay time = 0 s
<2> As for the switch-in delay, refer to [1024]. p0607 = 0 suppresses fault F07016.
<3> For KTY and "No sensor", temperature as defined in the model.
<4> Applies only for VECTOR.
<5> P0606 does not work for alarms via p0616.
<6> The relevant rated response temperature in °C depends on the temperature sensor chosen by the motor manufacturer.
<7> The assignment of temperature channels T1...T4 depends on the hardware used.
1
2
DO: SERVO, VECTOR
Signals and monitoring functions - Thermal monitoring, motor
MotTMod T_environ
r0630
MotTMod T_iron
r0631
MAX
MotTMod T_copper
r0632
MotTMod T_rotor
r0633
1
r4620[0] r4620[1] r4620[2] r4620[3]
Mot temp_sensortyp
Mot temp_senstyp
p0601[M]
Temp.
Temp.
Temp.
channel
channel
channel
1
2
p4600[E] p4601[E] p4602[E] p4603[E]
0 = No sensor
Configuration
1 = PTC alarm and time
2 = KTY84
0 = no sensor
3 = KTY84 & PTC, for
10 = PTC fault
encoder only
11 = PTC alarm
4 = Bimetal NC contact
12 = PTC alarm and time step
alarm with time step
20 = KTY84
for MM only
30 = Bimetal NC contact fault
31 = Bimetal NC contact alarm
10 = Evaluation of
several temperature
32 = Bimetal NC contact fault/
channels
alarm with time step
3
4
T_mot gemessen
1
r0035
Mot temp fault thresh
p0605[M]
1
0
KTY sensor type
(threshold not applicable for PTC)
Mot TempAlrmThresh
p0604[M]
Mot temp alarm 1
Temp.
channel
3
4
M I N
1650
<6>
KTY
PTC
Sensor type
<3>
Mot temp_sens time
-140 °C
250 °C
5
fp_8016_01_eng.vsd
19.07.07 V02.05.01
p0610[M]
p0610 = 0: No response, only alarm, no reduction of I_max
p0610 = 1: Alarm and reduction of I_max and fault (F07011)
p0610 = 2: Alarm and fault (F07011), no reduction of I_max
<4>
Fault response
p0610 = 1
Suppress fault
&
I_max reduction
&
[1690.1][6640.2]
p0616[M]
p0606[M]
<1>
<5>
F07011
&
1
"Motor overtemperature"
T
0
1
r2135.12
1
A07910
"Motor overtemperature"
0
p0607[M]
1
r2135.14
<2>
A07016
T
0
"Motor temperature
sensor fault, fault"
A07015
"Motor temperature
sensor fault alarm"
A07820 "Temperature sensor not connected"
6
7
Function diagram
SINAMICS S
1.00 s
p0610 = 0
[2548.2]
[2548.2]
8
- 8016 -