Chapter 4: System Design and Configuration
Example 1: V2100 584/984 Mode
1
Find the Modbus address for User V location
V2100.
1. Find V memory in the table
2
2. Convert V2100 into decimal (1088).
3. Add the Modbus starting address for the mode (40001).
3
For Word Data Types...
Timer Current Value (V)
Counter Current Value (V)
4
V Memory, User Data (V)
Example 2: Y20 584/984 Mode
5
Find the Modbus address for output Y20.
1. Find Y outputs in the table.
2. Convert Y20 into decimal (16).
6
3. Add the starting address for the range (2048).
4. Add the Modbus address for the mode (1).
7
Outputs (Y)
Control Relays (CR)
8
Timer Contacts (T)
Example 3: T10 Current Value 484 Mode
9
Find the Modbus address to obtain the
current value from Timer T10.
10
1. Find Timer Current Values in the table.
2. Convert T10 into decimal (8).
3. Add the Modbus starting address for the mode (3001).
11
For Word Data Types...
Timer Current Value (V)
12
Counter Current Value (V)
V Memory, User Data (V)
13
Example 4: C54 584/984 Mode
Find the Modbus address for Control Relay
14
C54.
1. Find Control Relays in the table.
2. Convert C54 into decimal (44).
A
3. Add the starting address for the range (3072).
4. Add the Modbus address for the mode (1).
B
Outputs (Y)
Control Relays (CR)
C
Timer Contacts (T)
Determining the D D i i r r e e c c t t NET Address
D
Addressing the memory types for DirectNET slaves is very easy. Use the ordinary native
230
address of the slave device itself. To access a slave PLC's memory address V2000 via
240
DirectNET, for example, the network master will request V2000 from the slave.
250-1
260
4–40
DL205 User Manual, 4th Edition, Rev. B
PLC Address (Dec.)
128
V0 - V177
128
V1000 - V1177
1024
V2000 - V3777
1024 - 2047
320
Y0 - Y477
2048 - 2367
256
C0 - C377
3072 - 3551
128
T0 - T177
6144 - 6271
PLC Address (Dec.)
128
V0 - V177
128
V1000 - V1177
512 - 639
1024
V2000 - V3777
1024 - 2047
320
Y0 - Y477
2048 - 2367
256
C0 - C377
3072 - 3551
128
T0 - T177
6144 - 6271
PLC Address (Dec.) + Mode Address
V2100 = 1088 decimal
1088 + 40001 =
41089
+
Appropriate Mode Address
0 - 127
3001
30001
512 - 639
3001
30001
4001
40001
PLC Addr. (Dec.) + Start Address + Mode
Y20 = 16 decimal
16 + 2048 + 1 =
2065
1
1
1
1
1
1
PLC Address (Dec.) + Mode Address
TA10 = 8 decimal
8 + 3001 =
3009
+
Appropriate Mode Address
0 - 127
3001
30001
3001
30001
4001
40001
PLC Addr. (Dec.) + Start Address + Mode
C54 = 44 decimal
44 + 3072 + 1 =
3117
1
1
1
1
1
1
Input Register
Input Register
Hold Register
Coil
Coil
Coil
Input Register
Input Register
Hold Register
Coil
Coil
Coil