Chapter 5: Intelligent Box (IBox) Instructions
ECOM100 Write IP Address (ECWRIP) (IB-723)
1
ECOM100 Write IP Address will write the given IP Address to the ECOM100 module on a
leading edge transition to the IBox. See also ECOM100 IP Setup (ECIPSUP) IBox 717 to
230
setup ALL of the TCP/IP parameters in a single
2
instruction - IP Address, Subnet Mask, and
240
Gateway Address.
250-1
3
The Workspace parameter is an internal, private
260
register used by this IBox and MUST BE
4
UNIQUE in this one instruction and MUST
DS5
Used
NOT be used anywhere else in your program.
N/A
HPP
5
Either the Success or Error bit parameter will
turn on once the command is complete. If there
is an error, the Error Code parameter will report
6
an ECOM100 error code (less than 100), or a
PLC logic error (greater than 1000).
7
The IP Address is stored in Flash-ROM in the ECOM100 and the execution of this IBox will
disable the ECOM100 module for at least a half second until it writes the Flash-ROM.
8
Therefore, it is HIGHLY RECOMMENDED that you only execute this IBox ONCE on the
second scan. Since it requires a LEADING edge to execute, use a NORMALLY CLOSED
SP0 (STR NOT First Scan) to drive the power flow to the IBox.
9
In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the
ECOM100 circuit board.
10
ECWRIP Parameters
11
• ECOM100#: this is a logical number associated with this specific ECOM100 module in the
specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must
12
reference this logical number
• Workspace: specifies a V-memory location that will be used by the instruction
13
• Success: specifies a bit that will turn on once the request is completed successfully
• Error: specifies a bit that will turn on if the instruction is not successfully completed
14
• Error Code: specifies the location where the Error Code will be written
• IP Address: specifies the IP Address that will be written to the module
A
B
ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K
Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B
C
Error . . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B
Error Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
D
IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5–308
DL205 User Manual, 4th Edition, Rev. B
Parameter
DL205 Range
K0-255
See DL205 V-memory map - Data Words
See DL205 V-memory map
See DL205 V-memory map
See DL205 V-memory map - Data Words
0.0.0.1. to 255.255.255.254