Chapter 5: Standard RLL Instructions - Boolean
And (AND)
1
The And instruction logically ands a normally open
230
contact in series with another contact in a rung. The
240
status of the contact will be the same state as the
2
250-1
associated image register point or memory location.
260
And Not (ANDN)
3
The And Not instruction logically ands a normally
230
closed contact in series with another contact in a rung.
4
240
The status of the contact will be opposite the state of
250-1
the associated image register point or memory location.
260
5
Operand Data Type
6
Inputs
Outputs
7
Control Relays
Stage
8
Timer
Counter
Special Relay
9
Global
Global
10
In the following And example, when input X1 and X2 are on output Y5 will energize.
11
DS
Implied
DirectSOFT
HPP
Used
12
13
14
In the following And Not example, when input X1 is on and X2 is off output Y5 will
A
energize.
B
DirectSOFT
C
D
5–14
DL205 User Manual, 4th Edition, Rev. B
DL230 Range DL240 Range
A
X
Y
C
S
T
CT
SP 0-117, 540-577
GX
GY
X1
X2
X1
X2
aaa
aaa
0–177
0–477
0–177
0–477
0–377
0–377
0–377
0–777
0–77
0–177
0–77
0–177
0-137, 540-617
-
-
-
-
Handheld Programmer Keystrokes
Y5
$
OUT
V
GX
Handheld Programmer Keystrokes
Y5
$
OUT
W
ANDN
GX
OUT
Aaaa
Aaaa
DL250-1
DL260 Range
aaa
0–777
0–777
0–1777
0–1777
0–377
0–177
0-137, 540-717
0-137, 540-717
-
-
B
ENT
STR
1
C
ENT
AND
2
F
ENT
OUT
5
B
ENT
STR
1
C
ENT
2
F
ENT
5
aaa
0–1777
0–1777
0–3777
0–1777
0–377
0–377
0-3777
0-3777
Need help?
Do you have a question about the DirectLOGIC DL205 Series and is the answer not in the manual?