D2-04Td1, Dc Output - Automationdirect.com DirectLOGIC DL205 Series User Manual

Table of Contents

Advertisement

Chapter 2: Installation, Wiring and Specifications

D2-04TD1, DC Output

1
D2-04TD1 DC Output
2
Outputs per Module
Output Points Consumed
Commons per Module
3
Output Type
Operating Voltage
4
Peak Voltage
ON Voltage Drop
AC Frequency
5
Max Load Current
(resistive)
Max Leakage Current
6
Max Inrush Current
Minimum Load Current
7
8
Derating Chart
Points
4
9
3
2
1
10
0
0
10
20
32
50
68
11
Ambient Temperature (˚C/˚F )
12
24VDC
+
13
12--24VDC +
14
A
B
C
D
2–36
DL205 User Manual, 4th Edition, Rev. B
4 (current sinking)
8 points (only first 4 pts. used)
1 (4 I/O terminal points)
NMOS FET (open drain)
10.2-26.4 VDC
40 VDC
0.72 VDC maximum
N/A
4A/point
8A/common
0.1 mA @ 40 VDC
6A for 100 ms, 15A for 10 ms
50 mA
2A / Pt.
3A / Pt.
4A / Pt.
30
40
50 55
C ˚
86
104
122131
F ˚
Internally
0V
connected
24V
C
0
L
C
1
L
C
2
L
C
3
L
External DC Required
Base Power Required 5VDC
OFF to ON Response
ON to OFF Response
Terminal Type (included)
Status Indicator
Weight
Fuses
OUT
12- -24
VDC
0
1
2
3
D2--04TD1
10.2- - 26.4VDC
50mA- - 4A
C
+24V
C
0
L
C
1
L
C
2
L
C
3
L
D2--04TD1
12--24
VDC
24 VDC @ 20 mA max.
60 mA
1 ms
1 ms
Removable; D2-8IOCON
Logic side
2.8 oz. (80 g)
4 (1 per point)
(6.3 A slow blow, non-replaceable)
Inductive Load
Maximum Number of Switching Cycles per Minute
Load
Duration of output in ON s tate
Current
7ms
40ms
0.1A
8000
1400
0.5A
1600
300
1.0A
800
140
1.5A
540
90
2.0A
400
70
3.0A
270
4.0A
200
At 40 mS duration, loads of 3.0A or greater cannot be used.
At 100 mS duration, loads of 2.0A or greater cannot be used.
Find the load current you expect to use and the duration that the
output is ON. The number at the intersection of the row and column
represents the switching cycles per minute. For example, a 1A
inductive load that is on for 100 ms can be switched on and off a
maximum of 60 times per minute. To convert this to duty cycle
percentage use: (duration x cycles)/60. In this example,
(60 x .1)/60 = .1, or 10% duty cycle.
24VDC
--
+
Reg
0V
Output
L
6.3A
+
--
Common
100ms
600
120
60
35
--
--
--
--
--
To LE D
Optical
Is olator
Other
Circuits

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DirectLOGIC DL205 Series and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents

Save PDF