D2–12TR, Relay Output
D2-12TR Relay Output
Outputs per Module
Outputs Points Consumed
Commons per Module
Output Type
Operating Voltage
Peak Voltage
ON Voltage Drop
AC Frequency
Minimum Load Current
Max Load Current (resistive)
Max Leakage Current
Max Inrush Current
Base Power Required 5VDC
OFF to ON Response
ON to OFF Response
Terminal Type (included)
Status Indicator
Weight
Fuses
5--30 VDC
5--240 VAC
L
L
L
L
L
L
5--30 VDC
5--240 VAC
L
L
L
L
L
L
Chapter 2: Installation, Wiring and Specifications
12
16 (four unused, see chart below)
2 (6-pts. per common)
Relay, form A (SPST)
5-30 VDC; 5-240 VAC
30 VDC; 264 VAC
N/A
47 to 60 Hz
5 mA @ 5VDC
1.5 A/point; Max of 3A/common
0.1 mA @ 265 VAC
Output: 3A for 10 ms
Common: 10A for 10 ms
450 mA
10 ms
10 ms
Removable; D2-16IOCON
Logic side
4.6 oz. (130g)
(2) 4A slow blow, replaceable
Order D2-FUSE-4 (5 per pack)
OUT
RELAY
A
0
1
2
B
3
D2--12TR
CA
5- - 240VAC
0
1.5A50/60Hz
5- - 30VDC
4
5mA- - 1.5A
1
CA
0
5
4
2
1
5
NC
2
3
NC
3
NC
CB
CB
0
0
4
4
1
5
1
2
5
3
2
NC
3
D2--12TR
NC
Typical Relay Life (Operations)
Voltage/Load
24 VDC Resistive
24 VDC Solenoid
110 VDC Resistive
110 VDC Solenoid
220 VAC Resistive
220 VAC Solenoid
Addresses Used
Points
Used?
Yn+0
Yes
Yn+1
Yes
Yn+2
Yes
Yn+3
Yes
Yn+4
Yes
Yn+5
Yes
Yn+6
No
Yn+7
No
n is the starting address
Derating Chart
Points
12
0.5A / Pt.
8
0.75A / Pt.
4
4
5
0
0
10
20
32
50
68
Ambient Temperature (˚C/˚F )
Internal module circuitry
OUTP UT
L
COM
4A
5--30 VDC
5--240 VAC
DL205 User Manual, 4th Edition, Rev. B
Current
Closures
1A
500k
1A
100k
1A
500k
1A
200k
1A
350k
1A
100k
Points
Used?
Yn+10
Yes
Yn+11
Yes
Yn+12
Yes
Yn+13
Yes
Yn+14
Yes
Yn+15
Yes
Yn+16
No
Yn+17
No
1.25A / Pt.
1.5A / Pt.
30
40
50 55
C ˚
86
104
122131
F ˚
To LE D
2–49
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Need help?