Chapter 2: Installation, Wiring and Specifications
D2-08NA-2, AC Input
1
D2-08NA-2 AC Input
Inputs per Module
2
Commons per Module
Input Voltage Range
3
Peak Voltage
ON Voltage Level
4
OFF Voltage Level
AC Frequency
Input Impedance
5
Input Current
6
Minimum ON Current
Maximum OFF Current
7
Base Power Required 5VDC
OFF to ON Response
8
ON to OFF Response
Terminal Type (included)
Status Indicator
9
Weight
10
Derating Chart
Points
11
8
6
12
4
2
13
0
0
10
20
32
50
68
Ambient Temperature (˚C/˚F )
14
A
Internal module circuitry
B
INP UT
C
COM
D
220VAC
COM
2–34
DL205 User Manual, 4th Edition, Rev. B
8
1 (2 I/O terminal points)
170-265 VAC
265 VAC
150 VAC minimum
40 VAC maximum
47-63 Hz
18 k
@ 60 Hz
9 mA @ 220 VAC, 50 Hz
11 mA @ 265 VAC, 50 Hz
10 mA @ 220 VAC, 60 Hz
12 mA @ 265 VAC, 60 Hz
10 mA
2 mA
100 mA
5 to 30 ms
10 to 50 ms
Removable; D2-8IOCON
Logic side
2.5 oz. (70 g)
30
40
50 55
C ˚
86
104
122131
F ˚
V+
To LE D
Optical
Is olator
Operating Temperature
Storage Temperature
Humidity
Atmosphere
Vibration
Shock
Insulation Withstand Voltage
Insulation Resistance
Noise Immunity
RFI
220VAC
C
0
1
2
3
32ºF to 131ºF (0º to 55ºC)
-4ºF to 158ºF (-20ºC to 70ºC)
35% to 95% (non-condensing)
No corrosive gases permitted
MIL STD 810C 514.2
MIL STD 810C 516.2
1,500 VAC 1 minute (COM-GND)
10M
@ 500 VDC
NEMA 1,500V 1 minute
SANKI 1,000V 1 minute
150 MHz, 430 MHz
Internally
connected
C
4
5
6
7
Need help?
Do you have a question about the DirectLOGIC DL205 Series and is the answer not in the manual?