D2–04TRS, Relay Output
D2-04TRS Relay Output
Outputs per Module
Outputs Points Consumed
Commons per Module
Output Type
Operating Voltage
Peak Voltage
ON Voltage Drop
AC Frequency
Minimum Load Current
Max Load Current (resistive)
Typical Relay Life (Operations)
Voltage & Load Current
Type of Load
1A
24 VDC Resistive
500k
24 VDC Solenoid
100k
110 VAC Resistive
500k
110 VAC Solenoid
200k
220 VAC Resistive
350k
220 VAC Solenoid
100k
At 24 VDC, solenoid (inductive) loads over 2A cannot be used.
At 100 VAC, solenoid (inductive) loads over 3A cannot be used.
At 220 VAC, solenoid (inductive) loads over 2A cannot be used.
5--30 VDC
5--240 VAC
L
L
L
L
Chapter 2: Installation, Wiring and Specifications
4
8 (only 1st 4pts. are used)
4 (isolated)
Relay, form A (SPST)
5-30 VDC / 5-240 VAC
30 VDC, 264 VAC
0.72 VDC maximum
47 to 63 Hz
10 mA
4A/point; 8A/module (resistive)
2A
3A
4A
200k
100k
50k
40k
––
–
250k
150k
100k
100k
50k
–
150k
100k
50k
50k
––
––
OUT
0
1
2
3
D2--04TR S
5-240VAC
4A50/60Hz
5- - 30VDC
10mA- - 4A
NC
NC
NC
NC
C0
C0
0
0
L
C1
C1
1
1
L
C2
C2
2
L
2
C3
C3
3
L
3
D2--04TR S
Max Leakage Current
Max Inrush Current
Base Power Required 5VDC
OFF to ON Response
ON to OFF Response
Terminal Type (included)
Status Indicator
Weight
Fuses
Points
4
3
2
1
0
0
10
RELAY
32
50
OUTP UT
L
COM
5--30 VDC
5--240 VAC
DL205 User Manual, 4th Edition, Rev. B
0.1 mA @ 264 VAC
5A for < 10 ms
250 mA
10 ms
10 ms
Removable; D2-8IOCON
Logic side
2.8 oz. (80 g)
1 per point
6.3A slow blow, replaceable
Order D2-FUSE-3 (5 per pack)
Derating Chart
2A /
Pt.
3A /
Pt.
4A /
Pt.
20
30
40
50 55
˚
C
68
86
104
122 131
˚
F
Ambient Temperature (˚C/˚F )
Internal module circuitry
To LE D
6.3A
2–45
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D