MDS-E/EH Series Instruction Manual
4 Setup
(PR)
#2330
SV130 RPITS
Set the base reference mark intervals of distance-coded reference scale. When the distance-coded refer-
ence scale is not used, set to "0".
The interval of basic reference mark (SV130) and auxiliary interval (SV131) must be in the specified relation-
ship. Other settings cause the initial parameter error (alarm 37).
Following is the specified relationship.
The quotient of (SV130×1000) / SV131 must be 4 or more and leaves no remainder.
Related parameters: SV081/bit7,3, SV131, SV134 to SV137
---Setting range---
0 to 32767 (mm)
(PR)
#2331
SV131 DPITS
Set the auxiliary interval of reference mark in the distance-coded reference scale. When the distance-coded
reference scale is not used, set to "0".
The interval of basic reference mark (SV130) and auxiliary interval (SV131) must be in the specified relation-
ship. Other settings cause the initial parameter error (alarm 37).
Following is the specified relationship.
The quotient of (SV130×1000) / SV131 must be 4 or more and leaves no remainder.
Related parameters: SV081/bit7,3, SV130, SV134 to SV137
---Setting range---
0 to 32767 (μm)
#2332
SV132
Not used. Set to "0".
#2333
SV133
Not used. Set to "0".
#2334
SV134 RRn0
Set this parameter to operate distance-coded reference check when using distance-coded reference scale.
During the distance-coded reference check initial setup (SV137:RAER=-1), set the following items on the NC
drive monitor screen after the distance-coded reference check initial setup warning A3 turns OFF.
SV134=Rn, SV135=Pn, SV136=MPOS
When reference point is set, the warning A3 turns OFF.
To enable the distance-coded reference check function, SV081/bit3=1setting and a battery option are need-
ed.
Related parameters: SV081/bit3,7, SV130, SV131, SV134 to SV137
---Setting range---
-32768 to 32767
#2335
SV135 RPn0H
Set this parameter to operate distance-coded reference check when using distance-coded reference scale.
During the distance-coded reference check initial setup (SV137:RAER=-1), set the following items on the NC
drive monitor screen after the distance-coded reference check initial setup warning A3 turns OFF.
SV134=Rn, SV135=Pn, SV136=MPOS
When reference point is set, the warning A3 turns OFF.
To enable the distance-coded reference check function, SV081/bit3=1setting and a battery option are need-
ed.
Related parameters: SV081/bit3,7, SV130, SV131, SV134 to SV137
---Setting range---
-32768 to 32767
Base reference mark interval
Auxiliary reference mark interval
Distance-coded reference check / revolution counter
Distance-coded reference check /position within one
rotation High
161
IB-1501229-F