MDS-E/EH Series Instruction Manual
4 Setup
#2222
SV022 OLL
Set the "Overload 1" (Alarm 50) current detection level as percentage to the stall current.
Normally set this parameter to "150". (For Mitsubishi adjustment.)
Related parameters: SV021
---Setting range---
110 to 500 (Stall current %)
#2223
SV023 OD1
Set the excessive error detection width in servo ON.
When set to "0", the excessive error alarm detection will be ignored, so do not set to "0".
<Standard setting value>
OD1=OD2= (Rapid traverse rate [mm/min]) / (60×PGN1) / 2 [mm]
Related parameters: SV026
---Setting range---
0 to 32767 (mm)
However, when SV084/bitC=1, the setting range is from 0 to 32767 (μm).
#2224
SV024 INP
Set the in-position detection width.
Set the positioning accuracy required for the machine.
The lower the setting is, the higher the positioning accuracy will be. However the cycle time (settling time)
becomes longer.
The standard setting value is "50".
---Setting range---
1 to 32767 (μm)
IB-1501229-F
Overload detection level
Excessive error detection width during servo ON
In-position detection width