4. PARAMETERS
4.1.13 Encoder output pulses
No.
Symbol
PA15
*ENR
Encoder output pulses
PA16 *ENR2 Encoder output pulse electronic gear
Used to set the encoder pulses (A-phase, B-phase) output by the servo amplifier.
Set the value 4 times greater than the A-phase or B-phase pulses.
You can use parameter No. PC13 to choose the output pulse setting or output division ratio setting.
The number of A/B-phase pulses actually output is 1/4 of the preset number of pulses.
The maximum output frequency is 4.6Mpps (after multiplied by 4). Use this parameter within this range.
(1) For output pulse designation
Set parameter No. PC13 to "
Set the number of pulses per servo motor revolution.
Output pulse = set value [pulses/rev]
For instance, when parameter No. PA15 is set to "5600", the A/B-phase pulses actually output are as
indicated below.
A-phase/B-phase output pulses =
Parameter
Name
POINT
This parameter is made valid when power is switched off, then on after setting.
0
" (initial value).
5600
= 1400[pulse]
4
Servo motor
M
Parameter No. PA15
Feedback pulses
Encoder
Initial
Setting
value
range
4000
65535
0
65535
FBP
A-phase/B-phase
conversion
output pulses
4 - 16
Control mode
Unit
Internal
Position
1 to
pulse/
rev
0 to
Internal
speed
torque