Wago-I/O-System - WAGO 750-830 Manual

Modular i/o system bacnet/ip controller
Table of Contents

Advertisement

282 •
List of all BACnet Properties in Native Operation
Configuration_Files
6.12 Configuration_Files
Date Type
Objects
Description
6.13 COV_Increment
Data Type
Objects
Description
6.14 Database_Revision
Data Type
Objects
Description
Change_Of_State_Count, or Time_Of_State_Count_Reset
is present, then all of these properties must be present.
Binary Output:
A change in polarity does not lead to a change in state. If
one of the optional properties Change_Of_State_Time,
Change_Of_State_Count, or Time_Of_State_Count_Reset
is present, then all of these properties must be present.
BACnetARRAY[N] for BACnetObjectIdentifier
Device
This property is a BACnet field for BACnetObjectIdentifier.
Entries in the array identify the files within the device that
define the device's image that can be backed up. The content
of this property is only required to be valid during the
backup procedure.
REAL
Analog input, Analog output
This property of the type REAL specifies the minimum
change in the property Present_Value that will cause a
COVNotification to be issued to subscriber COV-clients.
This property is required if COV reporting is supported by
this object.
Unsigned
Device
This property, of type Unsigned, is a logical revision num-
ber for the device's database. It is incremented when an ob-
ject is created, an object is deleted, an object's name is
changed, an object's Object_Identifier property is changed,
or a restore is performed.

WAGO-I/O-SYSTEM 750

BACnet/IP Controller