WAGO 750-830 Manual page 132

Modular i/o system bacnet/ip controller
Table of Contents

Advertisement

132 •
BACnet/IP Controller 750-830
LED Signaling
Error code 6 " Node configuration error "
Error
argument
Error code 7 -not used-
Error code 8 -not used-
Error code 9 - not used -
Error code 10 "Error during PLC program processing"
Error
argument
Error description
5
Initialization error of an
application protocol
6
Maximum process im-
age size exceeded
7
IP address of the bus
coupler is repeated sev-
eral times in the network
8
Error during process
image generation
9
The project in WAGO-
I/O-PRO CAA differs
from the SYM_XML
file or the SYM_XML
file is missing. The con-
nection between
WAGO-I/O-PRO CAA
and BACnet is inter-
rupted.
Error description
1
Error while applying
the PFC runtime sys-
tem
2
Error while generating
the PFC inline code
3
An IEC task has ex-
ceeded the maximum
runtime, or the call
interval for the IEC
task could not be main-
tained (timeout)
Solution
1. Restart the fieldbus coupler by turning the power
supply off and on again.
1. Reduce the number of bus modules
1. Use an IP address that has not been used in the
network
1. Reduce the number of bus modules on the node
1. Check both the project in WAGO-I/O-PRO CAA
and the SYM_XML file. Both must match.
Solution
1. Restart the fieldbus coupler by turning the power
supply off and on again. 2. Please contact I/O
Support if the error continues.
1. Restart the fieldbus coupler by turning the power
supply off and on again.
2. Please contact I/O Support if the error continues.
1. Check the task configuration with regard to the set
call intervals and monitoring times.
WAGO-I/O-SYSTEM 750
BACnet/IP Controller