88 •
BACnet/IP Controller 750-830
Fieldbus Node Start-up
3.1.7.2.6
Deactivating the BootP Protocol
By default, the BootP protocol is activated in the controller. When the BootP
protocol is activated, the controller expects the BootP server to be perma-
nently available. If there is no BootP server available after a PowerOn reset,
the network will remain inactive.
You must deactivate the BootP protocol and set a fixed IP address. After that,
a BootP server is no longer necessary.
Deactivation of the BootP protocol is performed using the HTML pages stored
in the controller (see also Section 3.1.8.7).
Note
If the BootP protocol is deactivated after addresses have been assigned, the
stored IP address is retained, even after an extended loss of power, or when
the controller is removed.
1. Open the Web browser on your client PC (such as the Microsoft Internet
2. Enter the IP address for your fieldbus node in the address line of the
A dialog window then appears with a password prompt.
This is provided for secure access and entails three different user groups:
"admin", "guest" and "user".
3. As Administrator, enter the user name: "admin" and the password
A start page is then displayed in the browser window with information about
your fieldbus controller. You can navigate to other information using the hy-
perlinks in the left navigation bar.
Explorer) to have the HTML pages displayed.
browser and press Return.
"wago".
WAGO-I/O-SYSTEM 750
BACnet/IP Controller