Process Data Architecture for MODBUS/TCP
Vibration Velocity/Bearing Condition Monitoring VIB I/O
750-645
The Vibration Velocity/Bearing Condition Monitoring VIB I/O has a total of
12 bytes of user data in both the Input and Output Process Image (8 bytes of
module data and 4 bytes of control/status). The following table illustrates the
Input and Output Process Image, which have 8 words mapped into each im-
age. Word alignment is applied.
Input and Output Process Image
byte Destination
Offset
High Byte
0
-
1
D1
2
-
3
D3
4
-
5
D5
6
-
7
D7
Low Byte
C0/S0
Not used
D0
(log. Channel 1, Sensor input 1)
C1/S1
Not used
D2
(log. Channel 2 Sensor input 2)
C2/S2
Not used
D4
(log. Channel 3 Sensor input 1)
C3/S3
Not used
D6
(log. Channel 4 Sensor input 2)
Remark
Control/Status byte
(log. Channel 1, Sen-
sor input 1)
Data bytes
Control/Status byte
(log. Channel 2 Sen-
sor input 2)
Data bytes
Control/Status byte
(log. Channel 3 Sen-
sor input 1)
Data bytes
Control/Status byte
(log. Channel 4 Sen-
sor input 2)
Data bytes
WAGO-I/O-SYSTEM 750
BACnet/IP Controller