List of all BACnet Properties in Native Operation

Alarm_Value

6.4 Alarm_Value
Data Type
Object
Description
BACnetBinaryPV
Binary input
This property, of the type BACnetBinaryPV, specifies the
value that the Present_Value property must have before an
event is generated. This property is required if intrinsic re-
porting is supported by this object.
Conditions for Generating a TO-OFFNORMAL Event
A TO-OFFNORMAL event is generated under these condi-
tions:
• the Present_Value must maintain the value specified
by Alarm_Value for a minimum period of time,
specified in the Time_Delay property, and
• the TO-OFFNORMAL flag must be enabled in the
Event_Enable property.
Conditions for Generating a TO-NORMAL Event
Once equal, the Present_Value must become not equal to
this property before a TO-NORMAL event is generated un-
der these conditions:
• the Present_Value must remain not equal to the
Alarm_Value for a minimum period of time, speci-
fied by the Time_Delay property, and
• the TO-NORMAL flag must be enabled in the
Event_Enable property.