Modification_Date - WAGO 750-830 Manual

Modular i/o system bacnet/ip controller
Table of Contents

Advertisement

6.48 Modification_Date

Data Type
Objects
Description
6.49 Notification_Class
Data Type
Objects
Description
6.50 Notify_Type
Data Type
Objects
Description
6.51 Number_Of_APDU_Retries
Data Type
Objects
Description
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
List of all BACnet Properties in Native Operation
BACnetDateTime
File
This property, of type BACnetDateTime, indicates the last
time this object was modified. A File object shall be consid-
ered modified when it is created or written to.
Unsigned
Binary Input, Binary Output, Analog Input, Analog Output
This property, of type Unsigned, shall specify the notifica-
tion class to be used when handling and generating event
notifications for this object. The Notification_Class property
implicitly refers to a Notification Class object that has a No-
tification_Class property with the same value.
BACnetNotifyType
Binary Input, Binary Output, Analog Input, Analog Output
This property, of type BACnetNotifyType, shall convey
whether the notifications generated by the object should be
Events or Alarms.
Unsigned
Device
The Number_Of_APDU_Retries property, of type Un-
signed, shall indicate the maximum number of times that an
APDU shall be retransmitted. The default value for this
property shall be 3. If this device does not perform retries,
then this property is set to zero. If the value of this property
is greater than zero, a non-zero value is placed in the device
object APDU_Timeout property.
• 295