3.1.9.1 Fieldbus Status
Communication status via ETHERNET is indicated by the upper-LED group
('LINK/ACT', 'BT' 'MS', 'NS' and 'I/O').
Tab.
LED
LNK/ACT
BT
MS
NS
I/O
USR
A
B
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
-
: Fieldbus status
3
22
Color
Off
Green
Blinking
Off
Green
Green blinking
Red
Off
Green
Green flashing
Red, flashing
Red
Red/green (orange) flashing Self test
Off
Green
Green flashing
Red, flashing
Red
Red/green (orange) flashing Self test
Red/green (orange)
Red/green (orange)
Green
Green
BACnet/IP Controller 750-830
LED Signaling
Meaning
No network connection at Port 1
Network connection at Port 1 (link)
Data traffic at Port 1 (activity)
No BACnet data traffic
BACnet data traffic, ready
Incoming PTP BACnet data packet was ac-
cepted as valid and forwarded for further proc-
essing
No BACnet data traffic (Initialization)
No power supply
The system is operating correctly
The system is not yet configured
The system indicates a recoverable error
The system indicates an unrecoverable error
No IP address has been assigned to the system.
At least one connection has been set up.
No connection
An error has occurred in the communication
over the ETHERNET
Double IP address in the network
The "I/O" LED indicates the operational status
of the node and signals any errors.
The "USR" LED can be selected by a user pro-
gram in a programmable fieldbus controller.
Status of the system power supply
Status of power of the power jumper contacts
(position of LED determined by production)
• 125