The file already contains the following syntax:
Fig. 3-6: EA-config.xml
The fourth line contains the necessary information for the first bus module.
The entry MAP="PLC" assigns write access privileges to the IEC 61131-3
program for the first module.
If you wish to change the access rights, replace "PL" with "FB3" as the access
privileges from BACnet.
5. Then complete the fourth line for each individual module using this syntax
Note
It is imperative that the number of line entries matches the number of existing
hardware modules.
6. Save the file and reload it to the controller file system via the FTP client.
You can then begin with IEC 61131-3 programming.
Additional Information
For a detailed description of how to use the software, please refer to the
WAGO-I/O-PRO CAA manual. The manual available at
http://www.wago.com
! WAGO-I/O-PRO ! 759-333
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
Programming the PFC Using WAGO-I/O-PRO CAA
and set the corresponding assigned access privileges:
<Module ITEMNO="" MAP="(e.g..) PLC" LOC="ALL"> </Module>