76 •
BACnet/IP Controller 750-830
Data Exchange
3.1.6.5.2.2
Bit Access
Tab. 3-16: Bit access
Method
FC2
- Read Input Discrete
FC1 = FC2 + 0x0200
– Read Coils
FC15-
- Force Multiple Coils
MODBUS Addresses
decimal
hexadecimal
0...
0x0000 –
511
0x01FF
512...
0x0200 –
1023
0x03FF
Illegal address
0x0400 –
0x0FFF
4096 ...
0x1000 –
8191
0x1FFF
8192 ...
0x2000 –
12287
0x2FFF
12288 ...
0x3000 -
32767
0x7FFF
32768 ...
0x8000 -
34295
0x85F7
36864 ...
0x9000 -
38391
0x95F7
0...
0x0000 –
511
0x01FF
512...
0x0200 –
1023
0x03FF
Illegal address
0x0400 –
0x0FFF
4096...
0x1000 –
8191
0x1FFF
8192...
0x2000 –
12287
0x2FFF
12288...
0x3000 -
32767
0x7FFF
32768...
0x8000 -
34295
0x85F7
36864 ...
0x9000 -
38391
0x95F7
IEC 61131-
Addresses
%IX( DigitalOffSet + 0 ).0 ...
%IX( DigitalOffSet + 31).15
%QX( DigitalOffSet + 0 ).0 ...
%QX( DigitalOffSet + 31).15
not supported
%QX256.0 ...
%QX511.15
%IX256.0 ...
%IX511.15
%MX0.0 ...
%MX1279.15
%IX32.0 ...
%IX127.7
%QX32.0 ..
%QX127.7
%QX( DigitalOffSet + 0 ).0 ...
%QX( DigitalOffSet + 31).15
%QX( DigitalOffSet + 0 ).0 ...
%QX( DigitalOffSet + 31).15
not supported
%IX256.0 ...
%IX511.15
%IX256.0 ...
%IX511.15
%MX0.0...
%MX1279.15
%QX32.0 ..
%QX1275.15
%QX32.0 ..
% QX127.7
WAGO-I/O-SYSTEM 750
Description
phys. inputs (1)
phys. outputs (1)
PFC-OUT variables
PFC-IN variables
Flag area (Default: 8 kByte,
size variable)
phys. inputs (2)
phys. outputs (2)
phys. outputs (1)
PFC-IN variables
Flag area (Default: 8 kByte,
size variable)
phys. outputs (2)
BACnet/IP Controller