WAGO 750-830 Manual page 150

Modular i/o system bacnet/ip controller
Table of Contents

Advertisement

150 •
BACnet/IP Controller 750-830
BACnet Building Controller (B-BC)
3.1.12.2
"Native" Operation of the B-BC
If the BACnet/IP Controller is switched on, not all objects that are supported
by the system are present. In this still unconfigured state, the following objects
are present for the connected modules:
• Analog Input Object
• Analog Output Object
• Binary Input Object
• Binary Output Object
• Calendar Object
• Device Object
• File Object
• Scheduler Object
The analog and digital Input and Output Objects are linked with the module
data. A configuration or programming of the controller is not necessary for the
creation and linking of these objects in native operation. The creation of the
objects for the connected modules takes place automatically.
In native operation, the object name is formed from the object type, an under-
score and the instance number. For example, the instance number 2 indicates
that this is the second created object.
Example:
An analog output object with an instance number of 4 receives the object
name "AnalogOutput_4".
Note
A maximum of 1000 objects can be created in the 750-830 BACnet/IP Con-
troller.
Additional Information
In the BACnet Configurator, you have, among other things, the possibility of
changing object names. These must be unique within a device.
Additional Information
You can program objects that are not automatically created in the WAGO-
I/O-PRO CAA. You can obtain additional information on the Internet under
Documentation ! 750-830 ! Additional Information ! BACnet - Objects,
Properties, Services
In the following, all objects that are automatically created in the native area
are listed. Which of these objects are actually installed depends on the con-
nected modules.
WAGO-I/O-SYSTEM 750
BACnet/IP Controller