Description Of The Call Options; Indirect Start Via Wago-I/O-Check From The Operating System - WAGO 750 Manual

4fdi 24v profisafe
Table of Contents

Advertisement

WAGO I/O System 750
753-661/000-004 4FDI 24V PROFIsafe
If you have already assigned a password, then you have to enter the current
password and the new password.
If you do not know the current password, you can use the master password to
assign a new one. The master password is 16 characters long and is
)[4~>#%qM}x=,:$~.
To close WAGO Safety Editor, click the [Exit] button in the WAGO Safety Editor
toolbar.
7.3.4

Description of the Call Options

WAGO Safety Editor can be started with various call options. Depending on the
call option, WAGO Safety Editor is started in either ONLINE or OFFLINE mode.
In ONLINE mode, different communication media are available (serial
connection, TCP/IP connection, fieldbus connection).
Do not change the selected F I/O module or communication connection if
an application is open!
Changing the F I/O module to be parameterized or the communication
connection is not possible while WAGO Safety Editor is running. If you want to
parameterize a different F I/O module, or you want to change the communication
connection, close and restart WAGO Safety Editor.
Safety Editor instances
In ONLINE mode, only one instance of WAGO Safety Editor can be open. In
OFFLINE mode, as many instances of WAGO Safety Editor as you want can be
open.
7.3.4.1

Indirect Start via WAGO-I/O-CHECK from the Operating System

Launch WAGO-I/O-CHECK.
Select an F I/O module for parameterization from the displayed fieldbus node
configuration. Execute the Settings command in WAGO-I/O-CHECK in the
context menu of the F I/O module (node view or navigation). WAGO-I/O-CHECK
then starts WAGO Safety Editor 75x with the current language and
communication settings. WAGO Safety Editor starts in ONLINE mode.
Communication is performed over the serial connection or ETHERNET TCP/IP,
depending on the current communication setting in WAGO-I/O-CHECK.
Version 1.0.0, valid from HW/SW Version 01/01
Commissioning
59
Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

753-661/000-004

Table of Contents