WAGO 750-830 Manual page 70

Modular i/o system bacnet/ip controller
Table of Contents

Advertisement

70 •
BACnet/IP Controller 750-830
Data Exchange
3.1.6.2.4
Absolute Addressing
Direct presentation of individual memory cells (absolute addresses) based on
IEC 1131-3 is performed using character strings:
Tab. 3-13: Absolute addresses
such as word-by-word: %QW27 (28th word), bit-by-bit: %IX1.9 (10th bit in the 2nd word)
* The designator "X" for bits can be omitted
Note
The character strings for absolute addresses must be entered connected, i.e.
without spaces or special characters!
Addressing Example:
Bit
Byte
Word
Double word
Bit
Byte
Word
Double word
Bit
Byte
Word
Double word
Position
Prefix
1
%
2
I
Q
M
3
X*
B
W
D
4
Inputs
%IB28
Outputs
%QB10
%QD2 (top section)
Flag
%MB22
%MD5 (top section)
Designation
Introduces an absolute address
Input
Output
Flag
Single bit
Byte (8 bits)
Word (16 bits)
Double word (32 bits)
Address
%IX14.0 ... 15
%IB29
%IW14
%QX5.0 ... 15
%QB11
%QW5
%MX11.0 ... 15
%MB23
%MW11
%IX15.0 ... 15
%IB30
%IW15
%ID7
%QX6.0 ... 15
%QB12
%QW6
%QD3 (bottom section)
%MX12.0 ... 15
%MB24
%MW12
%MD6 (bottom section)
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
Commentary
Data width
%IB31
%QB13
%MB25

Hide quick links:

Advertisement

Table of Contents
loading