2.6.9 Wire Connection
All components have CAGE CLAMP® connections.
The WAGO CAGE CLAMP® connection is appropriate for solid, stranded
and finely stranded conductors. Each clamping unit accommodates one con-
ductor.
Fig. 2-9: CAGE CLAMP® Connection
The operating tool is inserted into the opening above the connection. This
opens the CAGE CLAMP
the opening. After removing the operating tool, the conductor is safely
clamped.
More than one conductor per connection is not permissible. If several conduc-
tors have to be made at one connection point, then they should be made away
from the connection point using WAGO Terminal Blocks. The terminal blocks
may be jumpered together and a single wire brought back to the I/O module
connection point.
Attention
If it is unavoidable to jointly connect 2 conductors, then a ferrule must be used
to join the wires together.
Ferrule:
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
Length
Nominal cross section
WAGO Product
®
. Subsequently the conductor can be inserted into
8 mm
2
1 mm
for 2 conductors with 0.5 mm
max.
216-103 or products with comparable properties
Mechanical Setup
Wire Connection
g0xxx08x
2
each
• 29