6.41 Max_APDU_Length_Accepted

Data Type
Objects
Description
6.42 Max_Pres_Value
Data Type
Objects
Description
6.43 Max_Segments_Accepted
Data Type
Objects
Description
6.44 Min_Pres_Value
Data Type
Objects
Description
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
List of all BACnet Properties in Native Operation
Unsigned
Device
This property, of type Unsigned, is the maximum number of
octets that may be contained in a single, indivisible applica-
tion layer protocol data unit. The value of this property shall
be greater than or equal to 50. The value of this property is
also subject to the limitations of the data link technology
used.
REAL
Analog input, Analog output
This property, of type REAL, indicates the highest number
in engineering units that can be reliably obtained for the
Present_Value property of this object.
Unsigned
Device
The Max_Segments_Accepted property, of type Unsigned,
shall indicate the maximum number of segments of an
APDU that this device will accept.
REAL
Analog input, Analog output
This property, of type REAL, indicates the lowest number in
engineering units that can be reliably obtained for the Pre-
sent_Value property of this object.