WAGO 750-830 Manual page 144

Modular i/o system bacnet/ip controller
Table of Contents

Advertisement

144 •
BACnet/IP Controller 750-830
BACnet Building Controller (B-BC)
3.1.12.1.1.2
Alarm and Event Management BIBBs
These BIBBs prescribe the BACnet capabilities required to interoperably per-
form the alarm and event management functions.
Alarm and Event-Notification Internal-B (AE-N-I-B)
Device B generates notifications about alarms and other events.
BACnet Service
ConfirmedEventNotification
UnconfirmedEventNotification
Devices claiming conformance to AE-N-I-B must also support either Intrinsic
or Algorithmic reporting. Any device that supports the generation of event no-
tifications that require operator acknowledgment must support AE-ACK-B.
Alarm and Event-ACK-B (AE-ACK-B)
Device B processes acknowledgments of previously transmitted alarm/event
notifications.
BACnet Service
AcknowledgeAlarm
To support this BIBB the device must also support acknowledgeable alarms.
Alarm and Event-Information-B (AE-INFO-B)
Device B provides event information to device A.
BACnet Service
GetEventInformation
Alarm and Event-Enrollment Summary-B (AE-ESUM-B)
Device B provides event enrollments to device A.
BACnet Service
GetEnrollmentSummary
Requests
Execute
x
x
Requests
Execute
x
Requests
Execute
x
Requests
Execute
x
WAGO-I/O-SYSTEM 750
BACnet/IP Controller

Hide quick links: