WAGO 750-830 Manual page 119

Modular i/o system bacnet/ip controller
Table of Contents

Advertisement

PLC
Click the "PLC" link to access a Web site where you can define the PFC func-
tionality settings for your controller.
Use the function "Process image - Set outputs to zero if user program is
stopped" to define the status of the outputs when your application program
quits.
If there is a check in the box for this function, all outputs will be set to zero; if
there is no check, the outputs will retain their current value.
Use the function "Default webpage" to define that the page "Webvisu.htm" be
used as the starting page instead of the standard page "Status information" that
is displayed when WMBS is accessed.
Note
The "Webvisu.htm" page does not have any hyperlinks to other Web sites.
To deactivate this starting page function, or to go to other pages using hyper-
links, enter the IP address for your controller and the address for the original
starting page in the URL line of your browser with the following syntax:
http://IP address of your controller/webserv/Index.ssi.
Use the "I/O configuration - Compatible handling for ea-config.xml" to define
the procedure employed for writing privilege access to outputs. Here, note
whether a control system configuration has already been created and, if so,
whether this configuration is correct or not.
Handling for this is shown in the following table.
Control sys-
tem configu-
ration
in the project
none
correct
faulted
When the function "I/O configuration – Insert monitoring entries into
ea-config.xml" is activated, the current process values will also be shown for
the data channels that are displayed on the "I/O config" Web page.
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
Programming the PFC Using WAGO-I/O-PRO CAA
I/O configuration
(function activated)
Write privileges to the outputs of
all modules are assigned on the
basis of an existing ea-config.xml.
The ea-config.xml file must be
completely error-free, otherwise the
write privileges for all modules will
be assigned to the standard field-
bus.
Write privilege to the module outputs is taken from the control system
configuration. A corresponding ea-config.xml file is generated in the file
system.
The standard fieldbus is granted write privileges to the outputs of all the
modules.
BACnet/IP Controller 750-830
I/O configuration
(function deactivated,
standard setting)
The outputs for all modules are
assigned to the PLC. Any ea-
config.xml file that may already be
present is ignored and overwritten.
• 119