WAGO 750-830 Manual page 137

Modular i/o system bacnet/ip controller
Table of Contents

Advertisement

3.1.11 Technical Data
System data
System data ETHERNET
Number of controllers
Transmission medium
max. length of fieldbus segment
max. network length
Baud rate
Fieldbus coupler connection
Protocols
Serial system data (BACnet PTP)*
Baud rate
max. length of fieldbus segment
Fieldbus coupler connection
Programming
IEC 61131-3-3
BACnet device profile
Standards and regulations (see chapter 2.2)
EMC CE Immunity to interference
EMC CE Emission of interference
Vibration resistance
Shock resistance
Degree of protection
Approvals (see chapter 2.2)
Accessories
PC software
Miniature WSB Quick marking system
Technical Data
Number of bus modules
with bus extension
Configuration
Program memory
Data memory
Non-volatile memory (retain)
Voltage supply
Input current
Efficiency of the power supply
Internal current consumption
Total current for bus modules
Isolation
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
max
BACnet/IP Controller 750-830
Limited by ETHERNET specification
Twisted Pair S-UTP 100 W CAT 5
100 m acc. to IEEE 802.3 standard
acc. to IEEE 802.3 standard
10/100 Mbit/s
1 x RJ45, 1 x RS232
BACnet/IP, BACnet PTP, MODBUS/TCP (UDP), HTTP,
BootP, DHCP, DNS, SNTP, FTP, SNMP V1, SMTP
9600 baud ... 115 200 baud
15 m depending on the baud rate / on the cable (at 19200
baud)
1 x D-Sub 9 socket
WAGO-I/O-PRO CAA
IL, LD, FBD (CFC), ST, FC
B-BC (BACnet-Building-Controller)
in acc. with EN 61000-6-2 (2005)
in acc. with EN 61000-6-3 (2001) +A11:2004
acc. to IEC 60068-2-6
acc. to IEC 60068-2-27
IP 20
UL
(UL508)
C
US
Conformity marking
BACnet conformity test in preparation
WAGO BACnet Configurator
64
250
via PC
512 Kbytes
256 Kbytes
24 Kbytes (16 Kbytes retain, 8 Kbytes flag)
DC 24 V (-25 % ... +30 %)
500 mA at 24 V
87 %
300 mA at 5 V
1700 mA at 5 V
500 V system/supply
Technical Data
* available from software version 2
• 137

Hide quick links:

Advertisement

Table of Contents
loading