152 •
BACnet/IP Controller 750-830
BACnet Building Controller (B-BC)
3.1.12.2.2
Analog Output Object
The Analog Output object defines a standardized object whose properties rep-
resent the externally visible characteristics of an analog output.
The Analog Output Object and its properties are summarized in Tab. 3-29.
The properties are described in section 6.
Tab. 3-29: Properties of the Analog Output Object
Property
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Units
Min_Pres_Value
Max_Pres_Value
Resolution
Priority_Array
Relinquish_Default
COV_Increment
Time_Delay
Notification_Class
High_Limit
Low_Limit
Deadband
Limit_Enable
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
*corresponds to the item number of the module
Data type:
BACnetObjectIdentifier
CharacterString
BACnetObjectType
REAL
CharacterString
CharacterString
BACnetStatusFlags
BACnetEventState
BACnetReliability
BOOLEAN
BACnetEngineeringUnits
REAL
REAL
REAL
BACnetPriorityArray
REAL
REAL
Unsigned
Unsigned
REAL
REAL
REAL
BACnetLimitEnable
BACnetEventTransitionBits
BACnetEventTransitionBits
BACnetNotifyType
BACnetARRAY[3] for BACnet-
TimeStamp
Default Value
Writable via BACnet by
means of
-
-
Analog_Output_X
-
ANALOG_OUTPUT
-
-
-
*see footnote
WriteProperty
' '
WriteProperty
'000'
-
State_Normal (0)
-
0
WriteProperty
'0'
-
NO_UNITS (95)
WriteProperty
0
-
0
-
0
-
-
-
0
WriteProperty
0
WriteProperty
0
WriteProperty
0
WriteProperty
0
WriteProperty
0
WriteProperty
0
WriteProperty
'111'
WriteProperty
'111'
WriteProperty
'111'
-
Alarm (0)
WriteProperty
UNSPECIFIED
-
WAGO-I/O-SYSTEM 750