WAGO 750-830 Manual page 85

Modular i/o system bacnet/ip controller
Table of Contents

Advertisement

The examples shown contain the following information:
Tab. 3-17: BootP Table Information
Information
node1, node2
ht=1
ha=0030DE000100
ha=0030DE000200
ip= 10.1.254.100
ip= 10.1.254.200
T3=0A.01.FE.01
sm=255.255.0.0
The local network that is described in this description does not require a gate-
way. You can therefore apply the example "Example of entry with no gate-
way" here.
3. In the following text line, replace the 12-place hardware address located
4. In place of this, enter the MAC address for your own controller.
5. If you would like to specify a name for your fieldbus node, delete "node1"
6. To assign the controller a specific IP address, mark the IP address given
7. Since you do not need the second example "Example of entry with gate-
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
Meaning
Any name for a node can be specified here.
Here the hardware type of the network is specified.
For ETHERNET the hardware type is 1.
These numbers are explained in RFC1700.
Specify the hardware address (MAC ID) for the BACnet/IP controllers
here (hexadecimal).
Specify the IP address for the BACnet/IP controller here (decimal)
Specify the gateway address here (hexadecimal)
The subnet mask for the subnetwork to which the BACnet/IP controller
belongs can also be specified here (decimal).
behind "ha=" in this example.
node1:ht=1:ha=0030DE000100:ip=10.1.254.100
in the text and enter the node name you wish to use.
node1:ht=1:ha=0030DE000100:ip=10.1.254.100
here in the example after
"ip=" and enter your own IP address.
node1:ht=1:ha=0030DE000100:ip=10.1.254.100
way" here, place the number sign (#) in front of the text line in Example
2 as a comment symbol:
# node2:hat=1:ha=003 0DE 0002 00:ip=10.1.254.200:
This line will not be evaluated after this.
BACnet/IP Controller 750-830
Fieldbus Node Start-up
T3=0A.01.FE.01
• 85