WAGO 750-830 Manual page 90

Modular i/o system bacnet/ip controller
Table of Contents

Advertisement

90 •
BACnet/IP Controller 750-830
Fieldbus Node Start-up
Fig. 3-3: Port configuration
You are shown a list of all the protocols supported by the controller. By de-
fault, the BootP protocol is activated in the controller.
5. Click the box behind BootP to remove the check mark. You have now de-
You can also deactivate any other protocols that you no longer need in the
same manner, or select desired protocols and activate them explicitly.
Since communication for each protocol takes place via different ports, you can
have several protocols activated simultaneously; communication takes place
via these protocols.
6. Click on SUBMIT and then switch off the power to the controller (hard-
7. Proceed according to section 3.1.7.1.2 and assign a fixed IP address to the
The protocol settings are then saved and the controller is ready for operation.
If you have activated the MODBUS/TCP protocol, for example, you can now
select and execute required MODBUS functions using the MODBUS master
too, such as querying of the module configuration via register 0x2030.
If you have activated the WAGO-I/O-PRO for example, you can also program
the controller via ETHERNET link using WAGO-I/O-PRO CAA in line with
Standard IEC 61131-3.
activated the protocol.
ware reset), or press down the mode selector switch.
controller.
G083052e
WAGO-I/O-SYSTEM 750
BACnet/IP Controller

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents