WAGO 750-830 Manual page 257

Modular i/o system bacnet/ip controller
Table of Contents

Advertisement

2 Channel Digital Output Modules
750-501, -502, -509, -512, -513, -514, -517, -535, (and all variations),
753-501, -502, -509, -512, -513, -514, -517
2 Channel Digital Input Modules with Diagnostics and Input Process
Data
750-507 (-508), -522, 753-507
The 750-507 (-508), -522 and 753-507 digital output modules have a diagnos-
tic bit for each output channel. When an output fault condition occurs (i.e.,
overload, short circuit, or broken wire), a diagnostic bit is set. The diagnostic
data is mapped into the Input Process Image, while the output control bits are
in the Output Process Image.
750-506, 753-506
The 750-506, 753-506 digital output module has 2-bits of diagnostic informa-
tion for each output channel. The 2-bit diagnostic information can then be de-
coded to determine the exact fault condition of the module (i.e., overload, a
short circuit, or a broken wire). The 4-bits of diagnostic data are mapped into
the Input Process Image, while the output control bits are in the Output Proc-
ess Image.
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
Bit 7
Bit 6
Bit 5
Bit 7
Bit 6
Bit 5
Bit 7
Bit 6
Bit 5
Process Data Architecture for MODBUS/TCP
Output Process Image
Bit 4
Bit 3
Input Process Image
Bit 4
Bit 3
Bit 2
Output Process Image
Bit 4
Bit 3
Bit 2
I/O Modules
Bit 2
Bit 1
Bit 0
controls
controls
DO 2
DO 1
Channel
Channel
2
1
Bit 1
Bit 0
Diagnostic
Diagnostic
bit S 2
bit S 1
Channel 2
Channel 1
Bit 1
Bit 0
controls
controls
DO 2
DO 1
Channel 2
Channel 1
• 257

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents