4.2.1.2.1
Objects
BACnet offers a unified structure for different areas in the network. Thus,
field devices such as probes, controllers of the automation level or even com-
plex control and operating stations of the management level are modeled in
the object representation. The 25 objects are tailored specifically to the HVAC
sector for building automation services. They contain both physical inputs and
outputs and virtual objects.
Tab. 4-36: BACnet objects
Object
1
2
3
4
5
6
7
8
9
10 Command
11 Device
12 Event Enrollment
13 File
14 Group
15 Life-Safety-Point
16 Life-Safety-Zone
17 Loop
18 Multi-State Input
19 Multi-State Output
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
Accumulator
Analog Input
Analog Output
Analog Value
Averaging
Binary Input
Binary Output
Binary Value
Calendar
Fieldbus Communication
Function
Count value entry; counts values
Analog inputs, measures voltage, temperature,
etc.
Analog outputs, e.g. for setting controllers
Analog value; e.g. from a calculation
Average for calculations and statistics
Binary input, reports an event or disturbance
Binary output; alternates between two states
Binary value, virtual binary data time
Operating calendar, list of holidays and vacations
(Group) request to execute predefined activities
(e.g. a list of switching commands)
Device, information on the respective BACnet
device
Event category, defined reactions to events
File, transmits data
Group entry, grouped object values in the device
Hazard reporter, delivers information on proper-
ties with regard to notifications of danger
Security area, includes hazard reporting objects
according to certain criteria
Controller, performs regulation functions
Multi-level input, delivers reports on states such
as off/on, open/closed as a coded number
Multi-level output, delivers the output states of
commands