6.72 Status_Flags

Data Type
Objects
Description
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
List of all BACnet Properties in Native Operation
BACnetStatusFlags
Binary input, Binary output, Analog input, Analog output,
Scheduler
This property, of type BACnetStatusFlags, represents four
Boolean flags that indicate the general "health" of a binary
or analog input or output or a scheduler object. Three of the
flags (for the schedule object two objects) are associated
with the values of other properties of this object. A more de-
tailed status could be determined by reading the properties
that are linked to these flags. The relationship between indi-
vidual flags is not defined by the protocol.
{IN_ALARM, FAULT, OVERRIDDEN,
OUT_OF_SERVICE}
IN_ALARM has the following meaning:
• Binary Input/Output/Analog Input/Output:
logical FALSE (0) of the property Event_State has the
value NORMAL, otherwise logical TRUE (1).
• Schedule:
The value of this flag is logical FALSE (0).
FAULT has the following meaning:
Logical TRUE (1) if the Reliability property is present and
does not have a value of NO_FAULT_DETECTED, other-
wise logical FALSE (0).
OVERRIDDEN has the following meaning:
• Binary Input/Analog Input:
Logical TRUE (1) if the point has been overridden by
some mechanism local to the BACnet Device. In this
case, "overridden" is taken to mean that the Pre-
sent_Value and Reliability properties are no longer
tracking changes to the physical input. Otherwise, the
value is logical FALSE (0).
• Binary Output/Analog Output:
Logical TRUE (1) if the point has been overridden by
some mechanism local to the BACnet Device. In this
case, "overridden" is taken to mean that the properties
Present_Value and Reliability no longer represent the
physical output. Otherwise, the value is logical FALSE
(0).
• 307
Status_Flags