List of all BACnet Properties in Native Operation
Priority_Array
6.59 Priority_Array
Data Type
Objects
Description
6.60 Priority_For_Writing
Data Type
Objects
Description
6.61 Protocol_Object_Types_Supported
Data Type
Objects
Description
BACnetPriorityArray
Binary Output, Analog Output
This property is a read-only array that contains prioritized
values/commands that are in effect for this object. See sec-
tion 4.2.1.2.3.2 for a description of the prioritization mecha-
nism.
Unsigned (1...16)
Scheduler
This property defines the priority at which the referenced
properties are commanded. It corresponds to the 'Priority'
parameter of the WriteProperty service. It is an unsigned in-
teger in the range 1-16, with 1 being considered the highest
priority and 16 the lowest.
BACnetObjectTypesSupported
Device
This property, of type BACnetObjectTypesSupported, indi-
cates which standardized objects are supported by this de-
vice's protocol implementation. The list of properties sup-
ported for a particular object may be acquired by use of the
ReadPropertyMultiple service with a property reference of
ALL.
WAGO-I/O-SYSTEM 750
BACnet/IP Controller