BACnet/IP Controller 750-830
Programming the PFC Using WAGO-I/O-PRO CAA
3.1.8.2 Creating/Exporting the SYM_XML File
Note
If you are in the simulation mode you cannot perform configuration of sym-
bols or settings for generating the SYM_XML file. The category Symbol
configuration is not available for selection in this case.
You can make this category visible by selecting Online \ Logoff in the main
menu and removing the check mark in front of Simulation.
The SYM_XML file is a file that contains all project variables. This file is
necessary for the BACnet Configurator. Proceed as follows to create this file:
1. In the WAGO-I/O-PRO CAA software under Project \ Options select the
2. Place a check mark in the check box Generate XML Symbol table
3. Click the button Configure symbol file.... A dialog window then appears
4. Place a check mark in the check box Issue object variables. This check
Once these options have been activated, an SYM_XML file will be generated
automatically with project variables when a project is compiled.
Note
If the check mark in the box Issue object variables is gray, this means that it
has not been explicitly set. Click in the box again to make sure that the check
mark appears in black.
category Symbol configuration.
in which you can set the object attributes.
mark must appear in black!