WAGO 750-830 Manual page 32

Modular i/o system bacnet/ip controller
Table of Contents

Advertisement

32 •
Power Supply
System Supply
Attention
Resetting the system by switching on and off the system supply, must take
place simultaneously for all supply modules (coupler/controller and
750-613).
2.7.2.2 Alignment
Recommendation
A stable network supply cannot be taken for granted always and everywhere.
Therefore, regulated power supply units should be used in order to guarantee
the quality of the supply voltage.
The supply capacity of the coupler/controller or the internal system supply
module (750-613) can be taken from the technical data of the components.
Internal current consumption
Residual current for bus termi-
nals
*)
Example
The internal current consumption is indicated in the technical data for each
bus terminal. In order to determine the overall requirement, add together the
values of all bus modules in the node.
Attention
If the sum of the internal current consumption exceeds the residual current
for bus modules, then an internal system supply module (750-613) must be
placed before the module where the permissible residual current was ex-
ceeded.
*)
cf. catalogue W4 Volume 3, manuals or internet
*)
Current consumption via system voltage:
5 V for electronics of the bus modules and cou-
pler/controller
Available current for the bus modules. Provided by
the bus power supply unit. See coupler/controller
and internal system supply module (750-613)
Coupler 750-301:
internal current consumption:350 mA at 5 V
residual current for
bus modules :
sum I
:
(5V) total
1650 mA at 5 V
2000 mA at 5 V
WAGO-I/O-SYSTEM 750
BACnet/IP Controller

Hide quick links:

Advertisement

Table of Contents
loading