Technical Data
Technical Condition of the Devices
Mechanical strength acc. to IEC 61131-2
Test specification
IEC 60068-2-6 vibration
IEC 60068-2-27 shock
IEC 60068-2-32 free fall
*) QP: Quasi Peak
Note
If the technical data of components differ from the values described here, the
technical data shown in the manuals of the respective components shall be
valid.
Frequency range
Limit value
5 Hz ≤ f < 9 Hz
1.75 mm amplitude (permanent)
3.5 mm amplitude (short term)
9 Hz ≤ f < 150 Hz
0.5 g (permanent)
1 g (short term)
Note on vibration test:
a) Frequency change: max. 1 octave/minute
b) Vibration direction: 3 axes
15 g
Note on shock test:
a) Type of shock: half sine
b) Shock duration: 11 ms
c) Shock direction: 3x in positive and 3x in negative direc-
tion for each of the three mutually perpendicular axes of the
test specimen
1 m
(module in original packing)
WAGO-I/O-SYSTEM 750