WAGO 750-830 Manual page 186

Modular i/o system bacnet/ip controller
Table of Contents

Advertisement

186 •
Fieldbus Communication
ETHERNET
The BOOTP Client allows for dynamic configuring of the network parame-
ters:
Parameter
IP address of the client
IP address of the router
Subnet mask
IP addresses of the DNS
servers
Host name
When using the bootstrap protocol for configuring the node, the network pa-
rameters (IP address, etc... ) are stored in the EEPROM.
Note
The network configuration is only stored in the EEPROM when the BootP
protocol is used, although not if configuration is done via DHCP.
The BootP protocol is activated in the (programmable) fieldbus coupler or
controller by default.
When the BootP protocol is activated, the (programmable) fieldbus coupler or
controller expects a BootP server to be permanently present.
If, however, there is no BootP server available after a power-on reset, the net-
work remains inactive.
To operate the (programmable) fieldbus coupler or controller with the IP con-
figuration stored in the EEPROM, you must first deactivate the BootP proto-
col.
This is done via the web-based management system on the appropriate HTML
page saved in the (programmable) fieldbus coupler or controller, which is ac-
cessed via the "Port" link.
If the BootP protocol is deactivated, the (programmable) fieldbus coupler or
controller uses the parameters stored in the EEPROM at the next boot cycle.
If there is an error in the stored parameters, a blink code is output via the IO
LED and configuration via BootP is automatically switched on.
Meaning
Network address of the (programmable) fieldbus cou-
pler or controller
If communication is to take place outside of the local
network, the IP address of the routers (gateway) is indi-
cated in this parameter.
The Subnet mask makes the (programmable) fieldbus
coupler or controller able to differentiate, which parts of
the IP address determine the network and which the
network station.
Here the IP addresses can be entered by maximally 2
DNS servers.
Name of the host
WAGO-I/O-SYSTEM 750
BACnet/IP Controller