WAGO 750-830 Manual page 84

Modular i/o system bacnet/ip controller
Table of Contents

Advertisement

84 •
BACnet/IP Controller 750-830
Fieldbus Node Start-up
Note
It is also possible to assign IP addresses under other operating systems (e.g.
under Linux) as well as with other BootP servers.
Note
The IP address is assigned via straight-through cable, switches, hubs, or via
direct link using a crossover cable. Addresses cannot be allocated via router.
3.1.7.2.4.1
BootP Table
The BootP table is the database for the BootP server. This table is available as
a text file (bootptab.txt) on the client PC where the WAGO BootP server is in-
stalled.
Note
The WAGO BootP server must be installed correctly before the following
steps can be performed:
1. On your PC, go to Start and select the menu item Programs \ WAGO
2. Click on WAGO BootP server configuration.
You are then provided with an editable table "bootptab.txt".
At the end of the list that highlights possible abbreviations that can be used in
the BootP table, two examples are given, detailing the allocation of an IP ad-
dress:
• "Example of entry with no gateway"
• "Example of entry with gateway"
Fig. 3-12: BootP Table
Software \ WAGO BootP Server.
p012908d
WAGO-I/O-SYSTEM 750
BACnet/IP Controller

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents