WAGO 750-830 Manual page 87

Modular i/o system bacnet/ip controller
Table of Contents

Advertisement

3.1.7.2.5
Testing the Function of the Fieldbus Node
1. In order to check communication with the controller and for correct IP ad-
2. Type the command ping using the IP address you have assigned, with the
3. Press Return
The controller sends a reply to your client PC that is displayed in the DOS
prompt window.
Should the error message "Request timeout" appear, check your input against
the IP address you assigned.
4. If the test is successful, you can close the DOS command prompt window.
The node is now ready to communicate.
3.1.7.2.5.1
Reasons for Failed IP Address Assignment
• The controller MAC address does not correspond to the entry given in the
• The client PC on which the BootP server is running is not located in the
• Client PC and/or controller is/are not linked to the ETHERNET.
• Poor signal quality (use switches or hubs)
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
dress assignment, start the DOS prompt via Start / Programs / Command
prompt.
following syntax:
ping
[space]
XXXX . XXXX . XXXX . XXXX
Fig. 3-2: Example for a fieldbus node function test
"bootstrap.txt" file.
same subnet as the controller; i.e., the IP addresses do not match
Example: Client IP: 168.192.0.10 and controller IP: 10.1.254.5
BACnet/IP Controller 750-830
Fieldbus Node Start-up
• 87
G083070e