292 •
List of all BACnet Properties in Native Operation
Local_Date
6.37 Local_Date
Data Type
Objects
Description
6.38 Local_Time
Data Type
Objects
Description
6.39 Location
Data Type
Objects
Description
6.40 Low_Limit
Data Type
Objects
Description
Date
Device
The Local_Date property, of type Date, shall indicate the
date to the best of the device's knowledge. If the BACnet
Device does not have any knowledge of time or date, then
the Local_Date property shall be omitted.
Time
Device
The Local_Time property, of type Time, shall indicate the
time of day to the best of the device's knowledge. If the
BACnet Device does not have any knowledge of time or
date, then the Local_Time property shall be omitted.
CharacterString
Device
This property, of type CharacterString, indicates the physi-
cal location of the BACnet Device.
REAL
Analog input, Analog output
This property, of type REAL, shall specify a limit that the
Present_Value must fall below before an event is generated.
This property is required if intrinsic reporting is supported
by this object.
WAGO-I/O-SYSTEM 750
BACnet/IP Controller