EMC

The compliance of the drive modules with EMC directive is specified in the
ACSM1 hardware manual for the single drive configuration. Please notice
that different common DC configurations have not yet been tested from EMC
point of view. However the available mains filters can be used in the AC
supply of the common DC system, but the rules to meet different EMC
categories are not yet available.

Installation

Please see ACSM1 hardware manual for the installation (mechanical and
electrical) guidelines of the drive modules and external options.

Drive module settings

Parameter settings of ACSM1 drive modules connected to DC
o Disable fault function "CROSS CONNECTION" (par. 46.08), if
the external DC supply (other than ACSM1 drive module) is
used
o Disable over voltage control (par. 47.01), if resistor braking is
used.
o For braking chopper parameter settings, please see
parameter group 48.