Pulse Encoder Connection - ABB DCS880 series Hardware Manual

20 ... 5200 a
Hide thumbs Also See for DCS880 series:
Table of Contents

Advertisement

Pulse encoder connection

Connecting a pulse encoder to the DCS880 converter
On the SDCS-CON-H01 it is possible to select the supply voltage using jumper J4D.
Encoder supply
5 V
24 V
The wiring is shown in the figure below.
DIFFERENTIAL
SINGLE-ENDED
= twisted
pair
A
A
B
B
Z
Z
0V
+U
A
A
B
B
Z
Z
0V
+U
3ADW000462R0101 DCS880 Hardware Manual e a
Hardware configuration
SDCS-CON-H01
no sense
no sense
Commissioning hint:
If the drive's measured direction of
CON-H01
XENC:1
ChA+
rotation is wrong or does not
ChA-
XENC:2
correspond to the measured EMF
ChB+
XENC:3
speed, 7301 Motor speed feedback
XENC:4
ChB-
may appear during start-up.
XENC:5
ChZ+
XENC:6
ChZ-
If necessary correct it by exchanging
XENC:7
EGND
the field connections F1 and F2 or
XENC:8
+VENC
exchange tracks A+ and A-.
For single-ended encoders tracks A-
and B- must be exchanged.
CON-H01
ChA+
XENC:1
94.16 OnBoard encoder position
XENC:2
ChA-
XENC:3
ChB+
should look like this:
ChB-
XENC:4
XENC:5
ChZ+
65535
XENC:6
ChZ-
XENC:7
EGND
Forward
XENC:8
+VENC
65535
SF_CON-H01_001_encoder_a.ai
Reverse
J4D
0
0
DZ_LIN_008_forw-rev_a.ai
Electrical installation
41

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dcs880-s series

Table of Contents