Siemens Sinamics G120P Operating Instructions Manual page 90

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Electrical installation
4.8 Signal connections
Digital inputs
Table 4- 20
Digital inputs
Pin
Designation
5
DI 0
6
DI 1
7
DI 2
8
DI 3
16
DI 4
17
DI 5
69
DI COM
Max. connectable cross-section: 1.5 mm²
DI: Digital input; DI COM: Ground reference
1)
Digital outputs
Table 4- 21
Digital outputs
Pin
Designation
18
DO 0 NC
19
DO 0 NO
20
DO 0 COM
21
DO 1 NO
22
DO 1 COM
23
DO 2 NC
24
DO 2 NO
25
DO 2 COM
Max. connectable cross-section: 2.5 mm²
DO: Digital output; NO: Normally-open contact; NC: Normally-closed contact; COM: mid-position contact
1)
90
1)
Voltage: 24 VDC
Maximum current consumption: 15 mA
Potential separation: The reference potential is terminal 69
Switching level
0 -> 1: +11 V
1 -> 0: +5 V
Reference potential for DI 0 ... 5
1)
Contact type: Changeover contact
Max. switching voltage: 250 VAC, 30 VDC
Max. switching current:
- at 250 VAC: 2 A
- at 30 VDC: 5 A
Contact type: Normally-open contact
Max. switching voltage: 30 VDC
Max. switching current: at 30 VDC: 0.5 A
Contact type: Changeover contact
Max. switching voltage: 250 VAC, 30 VDC
Max. switching current:
- at 250 VAC: 2 A
- at 30 VDC: 5 A
Technical data
Technical data
Operating Instructions, 12/2014, A5E32923362A
Inverter cabinet units

Advertisement

Table of Contents
loading