Free Pdo Mapping For Example Of The Actual Current Value And Torque Limit - Siemens Sinamics G120P Operating Instructions Manual

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Operation
6.9 Communication over CANopen
6.9.4

Free PDO mapping for example of the actual current value and torque limit

You integrate the actual current value and torque limit into the communication via the free
PDO mapping.
The actual current value and the torque setpoint are transferred in TPDO1 and RPDO1,
respectively. TPDO1 and RPDO1 have already been specified by the Predefined Connection
Set.
Mapping the actual current value (r0068) with TPDO1
Procedure
Proceed as follows to accept the actual current value as send object in the communication:
1. Set the OV index for the actual current value:
first free OV index from the send data from the "Free objects" 5810 table
2. Map the OV index for the actual current value with PZD2:
– Set the COB-ID of TPDO1 to "invalid":
– Link the mapping parameter object 2 of TPDO1 (p8730[1]) with the OV index for the
– Set the COB-ID of TPDO1 to "valid":
r8751 shows which object is matched to which PZD:
PZD2 (r8751[1] ) = 5810 (actual current value)
3. Link the PZD send word 2 in the send word (p2051) with the actual current value:
p2051[1] = r0068[0]
292
p8720[0] = 800001B2 hex
actual current value:
p8730[1] = 58100010 hex (5810 = OV index, 00 = fixed value, 10 ≙ 16-bit value)