10.3

Maintenance

Servicing involves activities and procedures for maintaining and restoring the specified
condition of the device.
Required tools
The following tools are required for replacing components:
● Spanner or socket spanner (w/f 10)
● Spanner or socket spanner (w/f 13)
● Spanner or socket spanner (w/f 16/17)
● Spanner or socket spanner (w/f 18/19)
● Hexagon-socket spanner (size 8)
● Torque wrench 5 Nm to 50 Nm
● Screwdriver, size 2
● T20 torx screwdriver
● T25 torx screwdriver
● T30 torx screwdriver
A socket wrench kit with two long extensions is recommended.
Tightening torques for screw connections
The following tightening torques apply when tightening connections of operating current-
conducting parts (DC link / motor connections, general busbars), non-operating current-
conducting parts (ground connections, ground terminal connections), and general steel
threaded connections.
Table 10- 1
NOTICE
Screw connections for protective covers
The threaded connections for the protective covers made of Makrolon must only be
tightened with 2.5 Nm.
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Tightening torques for screw connections
Thread
Ground connections, protective
conductor connections, steel
(fault current-conducting)
M3
M4
M5
M6
M8
M10
M12
threaded connections
1.3 Nm
3 Nm
6 Nm
10 Nm
25 Nm
50 Nm
88 Nm
Maintenance and servicing
10.3 Maintenance
Plastic, busbars (operating current-
conducting)
0.8 Nm
1.8 Nm
3 Nm
6 Nm
13 Nm
25 Nm
50 Nm
455