Siemens Sinamics G120P Operating Instructions Manual page 189

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Control word 1 (STW1)
Control word 1 (bits 0 ... 10 in accordance with PROFIdrive profile and VIK/NAMUR, bits 11
... 15 specific to the inverter). See also function diagram 2441/2442.
Bit
Significance
Telegram 20
All other tele-
grams
0
0 = OFF1
0 → 1 = ON
1
0 = OFF2
1 = No OFF2
2
0 = Quick stop (OFF3)
1 = No quick stop (OFF3)
3
0 = Inhibit operation
1 = Enable operation
4
0 = Disable RFG
1 = Do not disable RFG
5
0 = Stop RFG
1 = Enable RFG
6
0 = Inhibit setpoint
1 = Enable setpoint
7
0 → 1 = Acknowledge faults
8, 9
Reserved
10
0 = No control via PLC
1 = Control via PLC
11
---
0 = Direction
1)
reversal
12
Reserved
13
---
1 = MOP up
1)
14
---
1 = MOP down
1)
15
CDS bit 0
Reserved
If you change over from another telegram to telegram 20, then the assignment of the previous telegram is kept.
1)
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
6.5 PROFIdrive profile for PROFIBUS and PROFINET
Explanation
The motor brakes with the ramp-down time p1121 of the
ramp-function generator. The inverter switches off the motor
at standstill.
The inverter goes into the "ready" state. If, in addition
bit 3 = 1, then the inverter switches on the motor.
Switch off the motor immediately, the motor then coasts
down to a standstill.
The motor can be switched on (ON command).
Quick stop: The motor brakes with the OFF3 ramp-down
time p1135 down to standstill.
The motor can be switched on (ON command).
Immediately switch-off the motor (cancel pulses).
Switch-on the motor (pulses can be enabled).
The inverter immediately sets its ramp-function generator
output to 0.
The ramp-function generator can be enabled.
The output of the ramp-function generator stops at the actu-
al value.
The output of the ramp-function generator follows the set-
point.
The inverter brakes the motor with the ramp-down time
p1121 of the ramp-function generator.
The motor accelerates with the ramp-up time p1120 to the
setpoint.
Acknowledge fault. If the ON command is still active, the
inverter switches to the "closing lockout" state.
The inverter ignores the process data from the fieldbus.
Control via fieldbus, the inverter accepts the process data
from the fieldbus.
Invert the setpoint in the inverter.
Increase the setpoint saved in the motorized potentiometer.
Reduce the setpoint saved in the motorized potentiometer.
Changes over between settings for different operation inter-
faces (command data sets).
Operation
Signal intercon-
nection in the
inverter
p0840[0] =
r2090.0
p0844[0] =
r2090.1
p0848[0] =
r2090.2
p0852[0] =
r2090.3
p1140[0] =
r2090.4
p1141[0] =
r2090.5
p1142[0] =
r2090.6
p2103[0] =
r2090.7
p0854[0] =
r2090.10
p1113[0] =
r2090.11
p1035[0] =
r2090.13
p1036[0] =
r2090.14
p0810 = r2090.15
189