PROFIenergy status requests
● List_Energy_Saving_Modes
Determines all supported energy-saving modes.
● GeLMode
Determines information about the selected energy-saving mode.
● PEM_Status
Determines the current PROFienergy status.
● PEM_Status_with_CTTO
Determines the current PROFienergy status, such as the PEMStatus, together with the
regular transition time to the operating state.
● PEldentify
Determines the supported PROFienergy commands.
● Query Version
Shows the implemented PROFienergy profile.
● Get_Measurement_List
This command returns the measured value IDs that can be accessed using the
"Get_Measurement_Values" command.
● Get_Measurement_List_with_object_number
This command returns the measured value IDs and the associated object number that
can be accessed using the "Get_Measurement_Values_with_object_number" command.
● Get_Measurement_ Values
The command returns the requested measured value using the measured value ID.
● Get_Measurement_Values_with_object_number
The command returns the requested measured values using the measured value ID and
the object number. The object number corresponds to the drive object ID.
Displaying
● r5600: Current energy-saving mode
● r5613: Interconnectable display of the PROFIenergy state
● A08800: PROFIenergy energy-saving mode active
General settings for PROFIenergy
● Minimum pause time: p5602
The inverter enters energy-saving mode only when the pause time sent with the
"Start_Pause" command is greater than or equal to the value for p5602.1. If the pause
time is less than p5602.1, the inverter ignores the command.
● Maximum pause time: p5606
Block PROFIenergy control commands
If you set p5611.0 = 1, you block the response of the inverter to PROFIenergy control
commands. In this case, the inverter ignores the PROFIenergy control commands.
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
6.6 PROFIenergy profile for PROFINET
Operation
205